LG UU61WR (60,000 BTU, 15 kW) - three-phase outdoor unit of a semi-industrial R32 system
Description LG UU61WR
The UU61WR: the top of the series
The UU61WR is the most powerful outdoor unit of LG's R32 semi-industrial series: 15 kW cooling, 16.9 kW heating, three-phase supply. The casing is 950 by 1380 by 330 mm with two fans; the compressor is a Dual Inverter, the refrigerant R32, and per the card the manufacturer country and country of origin are Korea, the warranty 24 months and the number of phases three. The weight is not given on the card; units of this output weigh roughly 100-115 kg, and the final figure comes from the data sheet. This is the upper limit of single-circuit equipment of this type: anything more powerful is built from several systems or on equipment of a different class. For many sites this model turns out to be the ceiling above which the task is no longer solved with a single machine.
Why three-phase 15 kW is the calmer configuration
The same circuit in single-phase form, the UU60WR (item 1819), draws 23-26 A from one phase; here the current is roughly 9-10 A on each of three. The difference shows up everywhere: a thinner cable, less heating of the contacts in the board, lower voltage drop on a long run and no imbalance where one phase of the building is overloaded. It matters for the authorised capacity too: a three-phase service usually has a higher limit, and 5-6 kW for air conditioning does not swallow the site's whole allowance. Inverter starting is soft, there are no inrush currents in the classic sense, so the breaker is selected by running current with headroom rather than by a starting multiple. The one condition is correct connection, with the phase sequence checked and a phase monitoring relay in the board, otherwise the loss of one phase turns into a compressor repair.
The limit of one circuit: when you move to another class of equipment
A single-circuit semi-industrial system means one outdoor unit and one indoor unit, with a shared temperature and a shared schedule for the whole circuit. While the task is one large hall that is enough; when there are several rooms each needing its own regime, the scheme stops working. There are three options: several separate smaller systems, a multi-split from the FM range where one outdoor unit serves several indoor units with their own controllers, or VRF-class equipment, which is not represented in this catalogue category. A practical rule: up to 15 kW and two or three zones, several simple systems are the better buy, being cheaper to install and independent in a breakdown; from five or six zones and several floors it is wiser to look at centralised solutions. We help compare the options from exactly that angle rather than by nominal capacity.
Air distribution at 15 kW
The indoor units for this circuit are the UM60R ducted unit (item 1833) of 1250 by 360 mm, the UT60R cassette (item 1841) of 840 by 840 mm and the UV60R ceiling-suspended unit (item 1847) 1600 mm long. The main engineering task at this capacity is not the cooling but the air: the unit moves a very large volume, and if it is delivered through two grilles the hall will have a noticeable draught. A ducted scheme needs six to eight supply grilles of the right free area and as many returns, otherwise the system resistance rises, the airflow drops and the coil starts to ice up. A 15 kW cassette distributes air four ways, but in a space with a low ceiling its stream reaches people while still cold, so the louvre positions are tuned to the layout and permanent workstations are kept out of the direct stream. A suspended unit gives a long stream along the space - in a workshop or a warehouse that is the most convenient of the three geometries.
Design, documentation and refrigerant accounting
For a commercial site of this size the installation follows a design rather than a verbal agreement: it is needed to agree the load with the electricity supplier, for the landlord and for later servicing. A three-phase connection may require an amendment to the technical conditions, and that question is settled before the equipment is ordered rather than after. The factory charge of a circuit of this output is measured in several kilograms of R32, and the actual quantity including the top-up for the pipe run is recorded in the handover documents. R32 is a flammable A2L refrigerant, so the minimum room volume per kilogram of charge is checked against the manufacturer's instructions; for large halls that limit is not critical, but for a small server room it can influence the choice. The rules for records and periodic leak checks on systems with fluorinated gases depend on the country, and we will advise what applies in your case.
Installation and commissioning
The base is calculated for a weight of around 110 kg plus the wind load on a 950 by 1380 mm plane; the frame is anchored, with vibration mounts beneath it. Clearances: 2 metres of front ahead of the fans, 50-100 cm above and 70 cm for access to the service panel. The pipework is first pressure-tested with nitrogen to the manual's figure and then evacuated for 60 minutes or more with a hold test and a vacuum gauge: on a circuit of this volume, saving time on these steps is the commonest cause of failures in the first season. Brazing is done under a nitrogen flow, otherwise the oxide scale from the inner surface of the pipes ends up in the compressor. At handover the phase voltages under load, the currents, the pressures, superheat and subcooling and the air temperatures in and out of the indoor unit are measured - and the record is handed to the client along with the warranty card.
Which jobs it fits and where it is out of place
The UU61WR is the choice for a space of roughly 140-180 m², or for a smaller area with large heat gains: a production area, a large shop, a gym, a dining hall, a print shop, a workshop. The conditions are a three-phase service with a matching capacity limit and a place for the unit with proper air access. Where the model is out of place: a site without three phases - that needs the single-phase UU60WR (item 1819); spaces with several zones at different temperatures; sites that need continuity of operation, where one circuit for the whole space is an unjustified risk. For a warehouse or workshop with doors standing open, comfort cooling does not work in principle. And if the calculation comes out above 15 kW, the model does not fit by definition - two systems or another class of equipment is planned instead.
How it differs from neighbouring models in this catalogue
The UU49WR (item 1822) is three-phase 13.5 kW in the same casing: one step down and noticeably easier to match to a space. The UU43WR (item 1821) is three-phase 12 kW and the UU37WR (item 1820) three-phase 10 kW in the lower 1170 mm casing. The UU60WR (item 1819) is the single-phase equivalent of this same 15 kW for sites without three phases. The UM60R (item 1833), UT60R (item 1841) and UV60R (item 1847) are the 15 kW indoor units: ducted, cassette and ceiling-suspended. If several rooms have to be served independently, the catalogue offers the FM57AH (item 1865) at 15.5 kW and the FM56AH (item 1862) multi-split systems, which distribute capacity among several indoor units - a different scheme with a different control logic.
Send us a floor plan, the ceiling height and the details of your supply - we will check whether one 15 kW circuit is enough and select an indoor unit for the UU61WR.