LG UU37WR (36,000 BTU, 10 kW) - three-phase outdoor unit of a semi-industrial R32 system
Description LG UU37WR
The UU37WR: the same 10 kW, but on three phases
The UU37WR is the outdoor unit of an LG R32 semi-industrial system with a circuit output of 10 kW cooling and 10.8 kW heating. It differs from the single-phase UU36WR (item 1816) in two things: a three-phase supply and a lower casing - 950 by 1170 by 330 mm instead of 950 by 1380 mm. A lower unit is easier to fit onto a plant platform or under a canopy, and together with the three-phase connection it means less current in each conductor. The compressor is a Dual Inverter, the refrigerant R32; per the card the manufacturer country and country of origin are Korea and the warranty 24 months. The weight is not stated on the card; units of this size weigh roughly 80-90 kg, and the final figure is taken from the data sheet.
What a three-phase connection gives you in practice
The same 10 kW circuit in single-phase form draws 15-17 A from one phase; in three-phase form it draws roughly 5-6 A from each. The consequences are simple: thinner cable, lower line losses, less heating of the breaker and no imbalance where one phase in the building is loaded while two sit idle. For a site that already has a three-phase service - a shop in a mall, a workshop, an office building - this is the normal engineering choice, with practically no extra cost. The second benefit concerns operation: a three-phase inverter holds compressor speed more steadily on an unstable network, because a sag on one phase is compensated by the other two. The key condition is correct connection: a five-conductor circuit with neutral and protective conductor, with the phase sequence checked before start-up.
Protection against phase loss and imbalance
Three-phase equipment is vulnerable to two typical network faults: loss of one phase and voltage imbalance between phases. If a phase disappears, the compressor tries to run on two and quickly overheats, so a phase monitoring relay is fitted in the board to disconnect the machine sooner than the thermal protection would. The second relay monitors sequence: if the phase order changes, for example after work in the switch room, some equipment starts in reverse, which for the machinery is a fault condition. Voltage imbalance of more than 5-7 per cent between phases shortens winding life, and it most often arises not from the air conditioner but from uneven loading by other consumers in the building. All these protections cost incomparably less than an inverter board and a compressor, so in a commercial space they are always specified.
Indoor units at 10 kW
The pair is chosen from three options: the UM36R ducted unit (item 1830) of 1250 by 270 mm, the UT36R cassette (item 1838) of 840 by 840 mm and 288 mm in height, and the UV36R ceiling-suspended unit (item 1844) 1600 mm long. The ducted unit gives the most freedom: air is distributed by grilles around the rooms while the unit itself stays invisible above the ceiling. A cassette is convenient in a square hall, because it distributes air four ways from one point and needs no ductwork. A suspended unit is the answer for a workshop, a warehouse or a hall with exposed services where there is nowhere to hide equipment: it mounts beneath the ceiling and throws a long stream along the space. We confirm the outdoor-indoor combination against LG's compatibility table: matching capacity does not guarantee that a pair is permitted.
A place for a 1170 mm unit
A height of 1170 mm rather than 1380 mm brings a real installation advantage: the unit more often fits under a canopy, into a well or behind a plant screen without reworking the structure. The rules stay the same: a rigid base, raising it 30-40 cm above the ground, a clear front of 1.5 metres ahead of the fans, 50 cm above and 60-70 cm on the service panel side. If a decorative screen is placed around the unit - and in commercial premises that is often a landlord's requirement - its free area has to be at least 70 per cent, otherwise the system suffocates. Vibration mounts under the frame and a flexible section in the pipework are mandatory: an 85 kg unit with two fans transmits vibration into the building structure better than one might expect. Access is planned not for the installation but for annual cleaning of the coil - that is what decides whether the system still holds its rated output in its third year.
Electrics and documentation
The circuit has five conductors, 380-400 V between phases, 50 Hz, with the cross-section chosen by calculation - usually 2.5-4 mm² copper per phase at this capacity, with its own breaker and a phase monitoring relay. Earthing and equipotential bonding are carried out to the design: for semi-industrial equipment that is no formality, because the inverter board is sensitive to induced voltages and static discharge. At handover the record captures phase voltages under load, currents, circuit pressures and the actual refrigerant top-up for the run length. Those data are the basis for future service and for warranty claims: without them, any complaint turns into a discussion of installation quality. Energy classes are not given on the outdoor unit's card, as they depend on the pair, and we state them when proposing a combination.
Which jobs it fits and where it is out of place
The UU37WR is the right choice for a shop, a cafe, an office, a workshop or a warehouse of 80-110 m² on a site with a three-phase service, where concealed or ceiling-mounted installation with wired control is wanted. It is also taken when refurbishing systems, where an old three-phase line already exists and nobody wants to rework the electrics. Where the model is out of place: a site without three phases - that needs the single-phase UU36WR (item 1816); spaces with several zones at different temperatures; sites that need continuity of operation and two independent circuits. For a space with major heat gains - a kitchen, machines, large south-facing glazing - 10 kW may turn out to be too little, and the sizing is done by heat gains rather than by floor area. If there are several rooms each needing its own temperature, a multi-split system is the alternative.
How it differs from neighbouring models in this catalogue
The UU36WR (item 1816) is the same 10 kW circuit but single-phase and in the taller 1380 mm casing. The UU43WR (item 1821) is three-phase 12 kW, the next step in capacity. The UU49WR (item 1822) is three-phase 13.5 kW and the UU61WR (item 1823) three-phase 15 kW, the top of the series. The UM36R (item 1830), UT36R (item 1838) and UV36R (item 1844) are the 10 kW indoor units: ducted, cassette and ceiling-suspended respectively. If the task is several rooms with independent control, the catalogue offers multi-split systems - the FM40AH (item 1860) at 11.2 kW and the larger FM models - which distribute capacity among several indoor units, and that is a fundamentally different scheme from one large circuit.
Tell us what supply you have and what will be in the space, and we will select an indoor unit for the UU37WR and advise which protections to fit in the board.