LG UT48R (48,000 BTU, 13.5 kW) - 840x840 mm cassette indoor unit for sales areas
Description LG UT48R
The UT48R: a 13.5 kW cassette
The UT48R is a cassette indoor unit from LG's R32 semi-industrial range, rated at 13.5 kW cooling and 15.5 kW heating. The casing is the standard one for the larger models in the series: 840 by 840 mm on plan, 288 mm deep, metal with plastic parts, 220-240 V, 50 Hz supply, R32 refrigerant and a Dual Inverter in the pair. Manufacturer country and country of origin are Korea, with a 24-month warranty. The PT-MCGW0 decorative panel (item 1916) is bought separately, as it is for the rest of the 24-60 kBTU range. Pipe diameters and the maximum run depend on the outdoor unit in the pair and come from the combination data sheet - we provide those figures with the quotation so that nobody orders copper on a guess.
Spacing when a hall holds several cassettes
A hall of 200-300 m² takes two or three cassettes, and what matters is not only the total kilowatts but how the units are spread across the area. The working rule: make the distance between neighbouring cassettes roughly twice the distance from a cassette to the wall, so that the streams overlap in the zone between them rather than meeting head-on. A cassette is not placed hard against a wall or a shop window - a stream hitting a vertical surface bounces back and shortens the throw on that side. Columns, tall shelving and display structures also break the stream, so the layout follows the actual equipment plan rather than the symmetry of the ceiling. Get the layout right and the temperature across the hall stays within a degree; get it wrong and it is hot by the windows and cold under the unit, while the owner concludes the system is underpowered.
Air in a sales hall: dust, filters and smoke detectors
A cassette continuously pulls the hall's air through itself, so whatever is in that air settles on the filter and the coil: textile lint in a clothes shop, flour dust in a bakery, fine abrasive in a builders' merchant. The standard filter is designed for domestic levels of dust, so in such premises the cleaning interval drops to two or three weeks and the coil is washed at least annually. A second, less obvious point is the interaction with fire alarms: a strong stream from a cassette can disperse smoke under the ceiling and delay a nearby smoke detector from triggering. Standards require a clearance between a supply opening and a detector, and that point is agreed with the alarm designer rather than settled on site with a tape measure. Third, the hall still needs fresh air from somewhere else: a cassette recirculates indoor air and does nothing about the carbon dioxide in it.
The outdoor unit: weight, facade and roof
The pair for the UT48R is built with the single-phase UU48WR (item 1818) or the three-phase UU49WR (item 1822), both at 13.5 kW cooling and 15.5 kW heating. A machine of this size has a mass that is not hung on aerated concrete or facing brick without calculation: brackets fix into the structural wall, and on a ventilated facade the fixings are set before the cladding goes on. On a roof the unit stands on a frame with resilient mounts, raised high enough that snow does not bury it in winter and air reaches it from all sides in summer. The load on the structure is agreed separately - in an older building that is a question for a structural engineer, not a formality. The pipe run down from the roof goes in a protected shaft with oil traps on the vertical sections, and its length is built into the calculation of additional refrigerant charge.
Consumption and night mode: where the money is saved
An inverter pair uses least when it runs for long periods at half output rather than switching on and off at full. The practical consequences: hold a steady setpoint instead of asking the system to pull the hall down from 30 degrees each morning, and set night mode as reduced output with the setpoint raised two or three degrees rather than as a shutdown. In a shop whose refrigeration runs around the clock that makes a visible difference over a month, because the cassette is not fighting a peak load every morning. A central controller - the AC EZ (item 1905) or the AC Smart 5 (item 1907) - lets you write a schedule and cap the setpoint range so that staff cannot call for 18 degrees in a heatwave. Finally, the cheapest saving of all is a clean filter and coil: a fouled unit draws more power, cools less and wears the compressor faster.
Alarm interlocks and working with ventilation
On sites with a fire alarm, air conditioning is normally required to stop on an alarm signal so that smoke is not driven around the hall: a volt-free contact is wired into the control circuit to shut the units down. That is done during the electrical work and recorded in the design, because the inspection asks about exactly this function rather than about the brand of equipment. The second point of interaction is mechanical ventilation: the cassette handles temperature while the ventilation handles air change, and if the two are set up independently the hall will alternately be overcooled and warmed by untreated supply air. The sound arrangement is for the ventilation unit to deliver treated air while the cassettes make up the difference, and the same catalogue carries LG's LZ-H energy recovery units (items 1888-1896) for that purpose. Coordinating the two systems at design stage is far easier than later working out why the hall is draughty and damp at once.
Commissioning and warranty: what you should be left holding
The 24-month warranty applies provided the equipment was installed and commissioned to the manufacturer's requirements, and that is no formality - most warranty refusals come down to installation faults. After start-up the client should keep: the commissioning record with the measured parameters, the actual pipe length and the amount of additional charge, the pressure test and evacuation records, and the warranty card with a date and stamp. It is worth photographing the pipe run before the ceiling is closed: that saves hours of diagnosis if a leak in a concealed section is suspected a year later. Recording the parameters at start-up - pressures, current, inlet and outlet temperatures - gives a baseline, so that a service visit two years on immediately shows what has changed. We advise assembling that file every time, even when the client's own crew does the installation, because without it any dispute comes down to one word against another.
Describe the hall - area, height, how the fixtures are arranged - and we will propose a cassette layout with the right spacing rather than a bare sum of kilowatts. The set with panels, outdoor units and central control is quoted as one document.