LG US36F (9.5 kW) - indoor unit for server rooms with year-round cooling
Description LG US36F
The US36F: a 9.5 kW indoor unit for server rooms
The US36F is a wall-type indoor unit from LG's server-room line: 9.5 kW cooling and 10.8 kW heating. The casing matches the smaller model: 1200 mm wide, 360 mm high, 265 mm deep; supply 220-240 V, 50 Hz, refrigerant R32, with a Dual Inverter compressor in the pair. Manufacturer country and country of origin are Korea, the warranty is 24 months and the casing is metal with plastic parts. The outdoor half of the pair is the UUD1.U30 (item 1851) at the same capacity, measuring 950 by 1380 by 330 mm. The card states the purpose plainly - for server rooms - which means the ability to cool all year rather than only in the warm season.
A kilowatt and a half of difference: when to take the larger pair
The 8 kW US30F and the 9.5 kW US36F share an indoor casing, so choosing between them is a choice of capacity, not of mounting type or installation work. The larger pair is taken in three situations: when the IT load already exceeds 6.5 kW, when the room has an external wall or window and picks up extra heat in summer, and when expansion is planned within two or three years. The third is the most common: racks are rarely left half empty, and equipment arrives faster than anyone planned. At the same time, margin for its own sake is not a virtue - in a lightly loaded room the machine runs in short bursts and holds humidity less well. The guide is simple: count the racks' actual consumption, add the heat from the UPS and the lighting, allow 20-30 per cent for growth, and take the pair that figure fits into.
Humidity in a server room: not only temperature
An air conditioner in a server room does not only cool, it dries the air, and in a technical space that cuts both ways. Too humid means condensation on cold surfaces and risk to electronics; too dry means static electricity, which is dangerous to boards during maintenance. The broadly comfortable band for server rooms is roughly 40-60 per cent relative humidity, and in this climate the problem more often appears in winter, when outdoor air is dry and the air conditioner dries it further. If people work in the room regularly or sensitive equipment is stored there, it is worth fitting a separate hygrometer and watching the readings through a season before deciding anything. Most small server rooms need no humidification, but knowing the actual numbers is useful - and cheaper than repairing a board killed by static.
Heat from the UPS and the batteries
Sizing often counts the servers and forgets the uninterruptible supplies, although they contribute noticeably to the heat load: part of their throughput becomes heat even on standby. The second point concerns the batteries: their life depends directly on temperature, and a few degrees above the recommended value shortens it appreciably. So in a room with a UPS and a large battery bank, cooling is planned not only to carry their heat but to keep the temperature in the battery zone steady. Where the battery room is separate, it often gets its own cooling circuit, because the temperature requirements there are stricter than for servers. We clarify these details during sizing, as they affect both the capacity and the position of the indoor unit.
Two units with rotation: how it is arranged
A server room with critical equipment gets two pairs, each able to carry the load alone, running alternately. Rotation solves three problems at once: even accumulated running hours, the ability to stop one machine for service without consequences, and automatic pick-up if one of them fails. Control uses the AC Smart 5 central controller (item 1907) with BACnet IP and Modbus TCP, with the PI485 PMNFP14A1 module (item 1904) connecting the outdoor units into the network. Where a simple arrangement without building management is wanted, an external rotation controller switches the units on a timer and brings both on if the temperature rises. What matters is that the rotation is automatic: schemes where someone swaps the machines by hand once a month work on no occasion when it actually matters.
Where to put the indoor unit in a cramped room
A room of ten to twenty square metres filled with racks leaves few options for an indoor unit, and each has consequences. It is not hung above the racks or above cable trays - any drainage problem in that position is expensive. Nor is it hung directly facing a rack front at close range: a cold stream straight into the servers' intakes disturbs their own airflow and leaves their sensors reading unevenly. The best position is a free wall, arranged so the air travels along the room and returns to the unit from the far side. Where the walls are entirely occupied, the alternative is a ducted or cassette unit in the void of an adjoining space, supplying through grilles - more expensive, but it settles the question of position for good.
Commissioning, paperwork and regular service
For a server room, commissioning is not a formality but the way the system's starting point is recorded: pressures, current, inlet and outlet temperatures, the actual pipe length and the top-up charge. Those figures go into the record, and a year later the service engineer sees at once what has changed instead of searching blind. Automatic restart after a power failure is checked and enabled - without it the air conditioner simply will not come back after an outage. Planned maintenance for equipment running around the clock happens twice a year: coil washing, pressure checks, drainage and electrical connections. Filters in a technical room are checked more often, monthly, and it is worth keeping a second set on site so the unit never runs while the first is drying.
Send a list of the equipment, the racks' consumption and a plan of the room, and we will calculate the load, the margin for growth and propose either one pair or two. We will also advise where to place the indoor unit so that drainage and airflow create no risk for the hardware.