LG CL18R (18,000 BTU, 5 kW) - low-static ducted indoor unit 190 mm high
Description LG CL18R
The CL18R: 5 kW in a 190 mm high casing
The CL18R is a ducted indoor unit of LG's R32 semi-industrial series rated at 5 kW cooling and 5.8 kW heating. The dimensions are the same as the smaller models in the series: 900 mm wide, 700 mm deep, 190 mm high, metal with plastic elements, supply 220-240 V, 50 Hz, with a Dual Inverter compressor in the pair. The manufacturer country and country of origin are Korea and the warranty 24 months. This model's card contains no pipe diameters, maximum pipe run or height difference - those fields hold dashes, and we say so openly. Judging by the neighbouring models in the series, the 18,000 BTU class works to a 1/4 inch liquid pipe and a 1/2 inch gas pipe with a run of up to 20-30 metres, but we supply the final values from LG's combination table for the specific pair.
5 kW in a slim casing: what it means for the ductwork
The casing stayed the same as on the 2.5 kW unit while the output doubled - which means twice as much air passes through the same cross-section. There is one practical consequence: the duct layout for a CL18R has to be more generous than for the smaller models, otherwise duct velocity rises, noise appears and the fan's static pressure is not enough to overcome the resistance. For this capacity the main duct is taken at 250 by 150 mm or more, or 200 mm diameter and up if round, and the branches are sized with headroom rather than to the minimum. Long sections of flexible duct are not acceptable here: even 4-5 metres of flexible duct with two bends can remove a third of the airflow. If the layout demands a long, branched network, the better choice is the medium-static CM18R (item 1828) with the same 5 kW output.
A layout with three or four grilles
For a space of 45-55 m² the air is usually delivered through three or four supply grilles: that distributes the flow evenly and avoids a draught at any one point. The main duct runs down the centre with branches symmetrically to the grilles; each branch is sized for its own share of the airflow rather than made identical at a guess. The return duct is no smaller than the supply, often a single large grille with a filter in a corridor or a service area. Grilles with adjustable louvres allow the direction to be changed after installation, and for a sales floor that gets rearranged that matters more than it seems. Commissioning includes measuring the airflow at each grille: without measurements the layout works out however it happens to, and one zone takes half of all the cooling.
A space of 45-55 m²: where this capacity belongs
5 kW is the typical figure for a small sales floor, a pharmacy, an open-plan office of six to eight workstations, a beauty salon or a dental surgery. In all these cases a ducted scheme wins on more than looks: it allows the air stream to be kept away from above people's heads, which for a salon or a treatment room matters at the level of client complaints. For a space with heat gains - a kitchen, equipment, an illuminated display - 5 kW may only cover 30-35 m², and the sizing is done by those gains. A hall with south-facing panoramic glazing shifts the figure too: midday solar load adds 1-2 kW for every 10 m² of unshaded glass. We calculate this from the parameters of the space rather than from the rule of a kilowatt per ten square metres, which does not hold for commercial premises.
Where the temperature sensor sits
By default a ducted unit is controlled by the sensor in the return airflow, which means it sees the average temperature of what came back to it from the space. That is convenient for an even hall but introduces an error if the return grille was placed in a corridor or beside a door to the street: the unit will work from the temperature of transit air rather than of the occupied zone. The answer is a wired controller with its own sensor on the wall in the occupied zone, such as the PREMTB001 (item 1897) or PREMTBB01 (item 1898); the unit's settings then choose which sensor holds the setpoint. For a shop where the controller is better kept out of customers' sight, there is a variant with a remote sensor and the controller in a back room. It is a small thing, settled in five minutes at commissioning, but it decides whether the space feels comfortable at one and the same setpoint.
Pairing with an outdoor unit
By output the CL18R pairs with the UU18WR outdoor unit (item 1814) at 5 kW cooling and 5.8 kW heating, single-phase, in a casing of 870 by 650 by 330 mm. The circuit runs on R32; since the indoor unit's card gives no diameters or lengths, we take the exact values for the pair from the manufacturer's documentation and state them with the proposal. The current of such a system at 220-240 V is modest, of the order of 7-9 A, and a dedicated circuit with a breaker is enough without changing the site's authorised capacity. The outdoor unit is positioned to leave 1-1.5 metres of clear space in front of the fan and access to the service panel. We always verify the combination against LG's compatibility table - that is a matter of warranty rather than formality.
Which jobs it fits and where it is out of place
The CL18R suits a space of roughly 45-55 m² with a suspended ceiling and at least 280-320 mm of void: a sales floor, an office, a salon, a consulting room, a small restaurant room. It is also taken for two or three adjoining rooms on the same regime, where separate systems in each are not economically justified. Where the model is out of place: spaces without a suspended ceiling; layouts with long branched ductwork, for which the CM18R (item 1828) offers the same capacity with higher static pressure; spaces with several zones each needing its own temperature. For a restaurant kitchen a comfort-cooling ducted system is unsuitable altogether - that needs different equipment and a different ventilation logic. And if the area exceeds 60 m², you move up to the CL24R (item 1827) or to the larger UM series units.
How it differs from neighbouring models in this catalogue
The CL12R (item 1825) is 3.5 kW in the same casing and the CL09R (item 1824) 2.5 kW: steps down in capacity. The CL24R (item 1827) is 7 kW in a wider 1100 mm casing with a 1/4 inch liquid and 5/8 inch gas pipe and a run of up to 30 metres per its card. The CM18R (item 1828) has the same 5 kW output but is 270 mm high with higher static pressure for complex ductwork; it is the main alternative to this model. If there is no suspended ceiling, 5 kW can be had from the CT18R cassette (item 1836) or the MJ18PC wall unit of a multi-split system (item 1873). The outdoor unit for this model is the UU18WR (item 1814), the same one that works with the CT18R and the CM18R.
Tell us the area, the layout and the ceiling void - we will size the ductwork for the CL18R and give you the exact pipe diameters from LG's combination table.